Description
- Place of Origin : China
- Brand Name : OEM brand
- Model Number : DZ47LE-100
- Type : Earth Leakage
DZ47LE-100 Residual current device 80A 100A 1P+N 2P 3P 3P+N 4P 230V 400V 30mA 100mA 300mA DZ47LE Residual Current Circuit Breaker
1. Application
DZ47LE-100 is applicable to a line of AC 50Hz/60Hz, rated voltage 230V for single pole two-wire, 2-pole or 400V for 3-pole, 3-pole 4-wire, 4-pole and rated current up to 40A. It can protectthe line and motor from overload and short circuit. It can also be used for infrequent line conver-sion and infrequent motor start. It conforms with the standards of IEC60947-2.
2. Main Technical Parameter
Type | DZ47LE-100 | |
Pole | 1P+N, 2P | 3P, 3P+N, 4P |
Rated current (A) | 63,80,100 | |
Rated voltage(V) | 230 | 400 |
Rated short circuit breaking capacity Icn(KA) | 6 | |
Rated residual making/breaking capacity Im(A) | 2000 | |
Rated residual action current In(A) | 0.03,0.1,0.3 | |
Rated residual non-action current Ino(A) | 0.5In | |
Over voltage protection grade | 280V±5% |
3. Applicable conducting wire
Rated current(A) | 63 | 80 | 100 |
Nominal cross section of wire mm2 | 16 | 25 | 35 |
4. Residual current breaking time
In(A) | In(A) | Breaking time(s) when equals to rating following | ||||
In | 2In | 5In | 5,10,20,50,100,200,500a(A) | Itb | ||
6-63 | 0.03, 0.05, 0.1, 0.3 | 0.1 | 0.06 | 0.04 | 0.04 | 0.04 |
5. The over-current protection property
Ambient Temperature | Initial Status | Test Current | Expected Result | Expected Result | NOte |
40±2oC | Cold position | 1.05In(In≤63A) | t≤1h | Non-release | – |
Cold position | 1.05In (In[63A) | t≤2h | Non-release | – | |
Carried out immedi-ately after previous test | 1.30In(In≤63A) | t < 1h | Release | Current smoothlyrises to specified value within 5s | |
1.30In (In>63A) | t< 2h | Release | |||
-5~+40oC | Cold position | 8.00In | t≤0.2s | Non-release | – |
Cold position | 12.00In | t < 0.2s | Non-release | – |
6. Dimension